Product specification |
Input |
Voltage range
|
100-250VAC |
Frequency |
50/60Hz |
Input current |
40A / 230VAC |
LEAKAGE CURRENT(max.) |
0.75mA / 240VAC |
Output |
Voltage |
48 VDC |
Output current |
0.52 A |
Ripple |
180mVp-p |
Over voltage protection |
Yes (clamp by Zener diode). |
Over current protection |
130 ~ 180% rated
output power
Protection type : Hiccup mode, recovers automatically after fault
condition is removed |
Over load protection |
105 ~ 135% rated
output voltage
Protection type : Recovers automatically after fault condition is
removed |
Temperature coefficient |
0.04%/C
(0~50C) |
Efficiency |
82% (Typ.) |
Hold-up time |
16ms at full
load |
Line regulation |
1% (Line
regulation is measured from low line to high line at rated load) |
Load regulation |
2% (Load
regulation is measured from 20% to 100% rated load) |
General |
MTBF |
500Khrs min.
MIL-HDBK-217F(25C) |
Environmental |
Operating Temperature |
0 C ~ +50C |
Storage Temperature |
-20 C ~ +85C |
Humidity |
20% ~ 90% RH,
non-condensing |
Derating |
Derated from
100% at +38 C |
SAFETY and EMC |
Safety
standards |
UL60950-1,
CSA C22.2, TUV EN60950-1, BSMI CNS14336 approved |
Withstand
voltage |
I/P-O/P:3KVAC
, I/P-FG:1.5KVAC |
Isolation
resistance |
I/P-O/P,
I/P-FG:100M Ohms / 500VDC / 25 / 70% RH |
EMI
conduction and radiation |
Compliance
to EN55022 class B, FCC PART 15 / CISPR22 class B, CNS13438 class B |
Harmonic
current |
Compliance
to EN61000-3-2,3 |
EMS
IMMUNITY |
Compliance
to EN61000-4-2,3,4,5,6,11, light industry level, criteria A |